The DGC-06: Digital Multi-Gas Controller System is designed to monitor and alert for toxic and combustible gases, vapors, and refrigerants across various gas measurements.
This controller system monitors and controls up to 128 gas types, 96 digital sensors, and 32 analog sensor options. It includes four freely adjustable alarm thresholds per connected sensor, meeting key safety code requirements such as EN50545-1 for CO monitoring, EN 378, and VBG 20 for NH3 monitoring.
Note: The DGC-06 operates exclusively with the Fixed Multi-Gas Detector Series or Combustible Fixed Gas Detectors.
Features
- Modular, user-friendly design suited for large facilities
- 128 gas sensor capacities
- Four adjustable alarm thresholds per sensor
- Five menu languages and adjustable settings
- Configurable relays for various alarms
- Alarm activation by rising or falling gas concentrations
- PCE06 Software connector at the controller module
- Flexible configuration with programmable parameters and set points
- Warning buzzer/LED alarm with fault and operation options
- Broad BMS compatibility
- SIL2 Level Compliance
Specifications
- Measurement Range: Dependent upon gas sensors selected
- Housing Type C/E: Plastic Housing with View Cover
- Gas Type: Dependent upon gas sensors selected
- Installation: Wall Mounted
- Ingress Protection: IP65
- Knockouts for Cable Entry: Standard 6× M20/25
- Storage Temp Range: 32 °F to 104 °F (0 °C to +40 °C)
- Temperature Range: 23 °F to 104 °F (-5 °C to +40 °C)
- Power Supply: 90/230 V AC, 50/60 Hz; 24 VDC ± 20 %
- Humidity Range: 15-95 % RH non-condensing
- Tension for external analog transmitter: 24 VDC ±20 %, max130 mA - per sensor
- Power Consumption: Min. 30 W, 0.15 A, max. ca. 160 W, 0.7 A, depending on the type
- Analog Input (4 to max. 32): 4–20 mA, overload and short-circuit proof, input resistance 130 µ
- Analog output (max 16) configurable for each input:
- 4–20 mA = measuring range
- Proportional, overload, and short-circuit proof, charge ≤ 500 µ
- 20–21.2 mA = over range
- 3.0–<4 mA = under range
- 2.0 mA = fault
- Relay (max. 32): 250 VAC, 5 A; 30 V DC, 2 A, potential-free, change-over (SPDT)
- Fault relay (1): 250 VAC, 5 A; 30 VDC, 2 A, potential-free, normally open contact (SPST)
- Transceiver: RS485 / 19200 Baud
- Dimensions: W × H × D - 11.7 × 10.2 × 5.5 in. | (298 × 260 × 140 mm)
- Weight: Min. 4.4 Ib. (2.7 kg), max. 28.7 Ibs. (13 kg) depending on type
- Weight: 1.32 lbs. (0.6 kg)
- Menu Language (selectable): German, English, French, or Italian
Regulations
- EMC Directive 2014/30/EU
- ANSI/UL 61010-1
- Low Voltage Directive 2014/35/EU
- EN 61010-1:2010
- EN 50271
- CAN/CSA-C22.2 No. 61010-1
- EN 50545-1
Warranty
Accessories
Options
- MSC-2 | Multi-Gas Fixed Gas Detector
- SC2-E1130-B-P-00 | NO2 Digital Sensor for MSC2
- SC2-E1110-A-P-00 | CO Digital Sensor for MSC2
- SC2-E1195-A2-P-00 | O2 Digital Sensor for MSC2
- SC2-E1194-A-P-00 | H2 Digital Sensor for MSC2
- SC2-I464-B-P-00 | CO2 Digital Sensor for MSC2